
Calculating Branch Circuit Size for Electric Tankless Water Heaters
Calculating Branch Circuit Size for Electric Tankless Water Heaters
Calculating the correct circuit size for a tankless water heater is a critical task for any licensed electrician. A proper continuous load calculation based on the NEC 125% rule is required to determine the minimum ampacity, which then dictates the appropriate overcurrent protection device (OCPD) and conductor size. Whole-house electric tankless water heater models are high-power appliances, often drawing over 100 amps, making a dedicated circuit mandatory. After determining the heater’s maximum amperage draw from its nameplate, you must multiply this value by 1.25. This result determines the minimum rating for the double-pole breaker and the required ampacity for the copper conductors. Finally, a total dwelling load calculation is essential to ensure the existing electrical service can handle the added demand, as a service panel upgrade is frequently necessary to complete a safe and compliant installation.
Why Proper Circuit Sizing is Non-Negotiable
The increasing adoption of electric tankless water heaters is driven by consumer demand for energy efficiency and on-demand hot water. However, these units have a significantly higher power demand than their tank-style counterparts. While a traditional storage-tank heater may only require a 30-amp circuit, a whole-house electric tankless water heater can draw anywhere from 40 to 170 amps. This substantial electrical load makes precise circuit sizing not just a recommendation, but a matter of safety and performance. Undersizing the circuit conductors or the overcurrent protection device can lead to overheating, creating a severe fire hazard and causing premature failure of the appliance.
Understanding Key Electrical Concepts for Installation
To perform a compliant installation, a journeyman electrician must be proficient in several core concepts outlined in the NEC code book. These principles form the foundation of safe and reliable circuit design for high-power appliances.
- Continuous Load and the NEC 125% Rule: The National Electrical Code (NEC) defines a continuous load as any load expected to operate for three hours or more. Since a water heater can run for extended periods, it falls into this category. The NEC 125% rule, found in articles 210.19(A)(1) and 422.13, mandates that the branch circuit conductors and the OCPD must have an ampacity of at least 125% of the appliance’s rated load. This buffer is crucial for managing heat buildup and ensuring the circuit’s long-term integrity.
- Ampacity and Wire Gauge (AWG): Ampacity is the maximum current, in amperes, that a conductor can carry continuously without exceeding its temperature rating. This capacity is determined by the conductor’s material (copper or aluminum), size (wire gauge (AWG)), and insulation type. The primary reference for this is the wire ampacity chart in NEC Table 310.16. For instance, the required 60 amp wire size will be different from that of a smaller circuit.
- Voltage Drop: Over long conductor runs, voltage drop can become a significant issue, leading to diminished performance and efficiency. For a high-draw appliance like a tankless heater, minimizing voltage drop is critical. NEC 210.19(A)(1) Informational Note 4 suggests limiting voltage drop to 3% for branch circuits. If a run is particularly long, selecting a larger wire gauge than the minimum required by ampacity calculations may be necessary to compensate.
Step-by-Step: Calculating the Circuit Size for a Tankless Water Heater
Follow these steps to accurately determine the correct branch circuit size for a tankless water heater, ensuring a safe and code-compliant installation on a 240-volt circuit.
- Determine the Maximum Amperage Draw (FLA): Locate the heater’s nameplate, which contains its electrical specifications. You are looking for the total wattage or the Full Load Amperage (FLA), also known as the maximum amperage draw. If only wattage is provided, calculate the amperage using the formula: Amps = Watts / Volts. For a 30,000-watt unit on a 240V supply, the calculation is 30,000W / 240V = 125A.
- Apply the NEC 125% Rule: Perform the continuous load calculation by multiplying the amperage from Step 1 by 1.25. Using the previous example: 125A x 1.25 = 156.25A. This is the minimum required ampacity for both the circuit conductors and the overcurrent protection.
- Select the Overcurrent Protection Device (OCPD): Based on the minimum ampacity calculated in Step 2, you must select the next standard-size overcurrent protection device (OCPD) from NEC Table 240.6(A). Since 156.25A is not a standard size, you would round up to the next available size, which is a 175A double-pole breaker. Trying to use a smaller breaker, like a 50 amp breaker or even a 150A breaker, would be a code violation and unsafe. For more details on breaker selection, review our guide on how to size a circuit breaker based on the NEC.
- Size the Conductor (Wire): Use the minimum ampacity from Step 2 (156.25A) to select the correct conductor sizing from NEC Table 310.16. Consulting the 75°C column for THHN copper conductors, you would find that 2/0 AWG copper wire is rated for 175 amps, making it suitable for this installation. Using an online size electrical wire calculator can be a helpful preliminary tool, but always confirm with the official NEC table.
- Perform a Total Dwelling Load Calculation: This is arguably the most critical and often overlooked step. Adding a load of this magnitude requires verifying that the home’s electrical service can handle it. A total dwelling load calculation (as specified in NEC Article 220) must be performed. Many older homes with 100A or 150A services will not have sufficient capacity, necessitating a service panel upgrade to 200A or greater.
Confidently install high-power appliances. Enroll in our load calculation courses.
Installation Considerations and Best Practices
Beyond the calculations, executing a professional installation involves several key practices. Adhering to these guidelines ensures the safety, reliability, and longevity of the system.
- Dedicated Circuit: An electric tankless water heater must be installed on its own dedicated circuit. It cannot share a circuit with any other outlets or appliances. Some larger models may even require multiple dedicated circuits, as specified by the manufacturer.
- Service Panel Capacity: Before starting any work, verify the main service panel has both the physical space for a new double-pole breaker and, more importantly, the electrical capacity to support the new load. Effective electrical load management starts with this assessment. Failure to do so can lead to an overloaded service, posing a risk to the entire property.
- Disconnecting Means: If the water heater is not within sight of the electrical panel, a disconnect switch is required at the unit’s location. This is a critical safety feature for maintenance and emergencies. Learn more about the requirements to install a water heater disconnect switch.
- Manufacturer’s Instructions: Always consult the manufacturer’s installation manual. While the NEC provides the minimum safety standards, the manufacturer may have specific requirements regarding wiring, clearances, or plumbing connections that must be followed.
For a comprehensive overview of the entire process, see our guide on how to install an electric tankless water heater. If you encounter issues with an existing unit, our article on troubleshooting an electric water heater can provide valuable insights.
Primary Sources
- National Fire Protection Association (NFPA) for the National Electrical Code (NEC)
Frequently Asked Questions (FAQ)
- How many dedicated circuits does an electric tankless water heater need?
- Most residential models require one or two dedicated 240-volt circuits. High-demand, whole-house units can sometimes require three or even four circuits. Always check the manufacturer’s specifications, as this dictates the exact number and required amperage of each circuit, such as a 60 amp wire size for each breaker.
- Can I use the old circuit from my tank-style water heater?
- In almost all cases, no. A standard tank water heater typically uses a 30-amp circuit with 10 AWG wire. An electric tankless water heater has a much higher maximum amperage draw, often requiring a 50 amp breaker, 60-amp, or larger circuit with correspondingly larger conductors (e.g., 6 AWG or 4 AWG copper).
- What is the risk of using the wrong wire gauge (AWG)?
- Using an undersized wire gauge (AWG) for the circuit’s amperage is extremely dangerous. The wire’s resistance will cause it to overheat, which can melt the insulation and create a fire hazard. It also leads to excessive voltage drop, causing the appliance to perform poorly and potentially shortening its lifespan.
- Is a service panel upgrade always required for a tankless water heater?
- A service panel upgrade is not always mandatory but is very common. Installing a powerful electric appliance requires performing a total dwelling load calculation as per NEC Article 220. If the new total load exceeds the capacity of the existing service (e.g., a 100A panel), an upgrade is necessary for a safe and compliant installation.
Continuing Education by State
Select your state to view board-approved continuing education courses and requirements:
Disclaimer: The information provided in this educational content has been prepared with care to reflect current regulatory requirements for continuing education. However, licensing rules and regulations can vary by state and are subject to change. While we strive for accuracy, ExpertCE cannot guarantee that all details are complete or up to date at the time of reading. For the most current and authoritative information, always refer directly to your state’s official licensing board or regulatory agency.



